1 Generic Thermal Sysfs driver How To
2 ===================================
3
4 Written by Sujith Thomas <sujith.thomas@intel.com>, Zhang Rui <rui.zhang@intel.com>
5
6 Updated: 2 January 2008
7
8 Copyright (c)  2008 Intel Corporation
9
10
11 0. Introduction
12
13 The generic thermal sysfs provides a set of interfaces for thermal zone
14 devices (sensors) and thermal cooling devices (fan, processor...) to register
15 with the thermal management solution and to be a part of it.
16
17 This how-to focuses on enabling new thermal zone and cooling devices to
18 participate in thermal management.
19 This solution is platform independent and any type of thermal zone devices
20 and cooling devices should be able to make use of the infrastructure.
21
22 The main task of the thermal sysfs driver is to expose thermal zone attributes
23 as well as cooling device attributes to the user space.
24 An intelligent thermal management application can make decisions based on
25 inputs from thermal zone attributes (the current temperature and trip point
26 temperature) and throttle appropriate devices.
27
28 [0-*]   denotes any positive number starting from 0
29 [1-*]   denotes any positive number starting from 1
30
31 1. thermal sysfs driver interface functions
32
33 1.1 thermal zone device interface
34 1.1.1 struct thermal_zone_device *thermal_zone_device_register(char *type,
35                 int trips, int mask, void *devdata,
36                 struct thermal_zone_device_ops *ops,
37                 const struct thermal_zone_params *tzp,
38                 int passive_delay, int polling_delay))
39
40     This interface function adds a new thermal zone device (sensor) to
41     /sys/class/thermal folder as thermal_zone[0-*]. It tries to bind all the
42     thermal cooling devices registered at the same time.
43
44     type: the thermal zone type.
45     trips: the total number of trip points this thermal zone supports.
46     mask: Bit string: If 'n'th bit is set, then trip point 'n' is writeable.
47     devdata: device private data
48     ops: thermal zone device call-backs.
49         .bind: bind the thermal zone device with a thermal cooling device.
50         .unbind: unbind the thermal zone device with a thermal cooling device.
51         .get_temp: get the current temperature of the thermal zone.
52         .get_mode: get the current mode (enabled/disabled) of the thermal zone.
53             - "enabled" means the kernel thermal management is enabled.
54             - "disabled" will prevent kernel thermal driver action upon trip points
55               so that user applications can take charge of thermal management.
56         .set_mode: set the mode (enabled/disabled) of the thermal zone.
57         .get_trip_type: get the type of certain trip point.
58         .get_trip_temp: get the temperature above which the certain trip point
59                         will be fired.
60         .set_emul_temp: set the emulation temperature which helps in debugging
61                         different threshold temperature points.
62     tzp: thermal zone platform parameters.
63     passive_delay: number of milliseconds to wait between polls when
64         performing passive cooling.
65     polling_delay: number of milliseconds to wait between polls when checking
66         whether trip points have been crossed (0 for interrupt driven systems).
67
68
69 1.1.2 void thermal_zone_device_unregister(struct thermal_zone_device *tz)
70
71     This interface function removes the thermal zone device.
72     It deletes the corresponding entry form /sys/class/thermal folder and
73     unbind all the thermal cooling devices it uses.
74
75 1.2 thermal cooling device interface
76 1.2.1 struct thermal_cooling_device *thermal_cooling_device_register(char *name,
77                 void *devdata, struct thermal_cooling_device_ops *)
78
79     This interface function adds a new thermal cooling device (fan/processor/...)
80     to /sys/class/thermal/ folder as cooling_device[0-*]. It tries to bind itself
81     to all the thermal zone devices register at the same time.
82     name: the cooling device name.
83     devdata: device private data.
84     ops: thermal cooling devices call-backs.
85         .get_max_state: get the Maximum throttle state of the cooling device.
86         .get_cur_state: get the Current throttle state of the cooling device.
87         .set_cur_state: set the Current throttle state of the cooling device.
88
89 1.2.2 void thermal_cooling_device_unregister(struct thermal_cooling_device *cdev)
90
91     This interface function remove the thermal cooling device.
92     It deletes the corresponding entry form /sys/class/thermal folder and
93     unbind itself from all the thermal zone devices using it.
94
95 1.3 interface for binding a thermal zone device with a thermal cooling device
96 1.3.1 int thermal_zone_bind_cooling_device(struct thermal_zone_device *tz,
97         int trip, struct thermal_cooling_device *cdev,
98         unsigned long upper, unsigned long lower, unsigned int weight);
99
100     This interface function bind a thermal cooling device to the certain trip
101     point of a thermal zone device.
102     This function is usually called in the thermal zone device .bind callback.
103     tz: the thermal zone device
104     cdev: thermal cooling device
105     trip: indicates which trip point the cooling devices is associated with
106           in this thermal zone.
107     upper:the Maximum cooling state for this trip point.
108           THERMAL_NO_LIMIT means no upper limit,
109           and the cooling device can be in max_state.
110     lower:the Minimum cooling state can be used for this trip point.
111           THERMAL_NO_LIMIT means no lower limit,
112           and the cooling device can be in cooling state 0.
113     weight: the influence of this cooling device in this thermal
114             zone.  See 1.4.1 below for more information.
115
116 1.3.2 int thermal_zone_unbind_cooling_device(struct thermal_zone_device *tz,
117                 int trip, struct thermal_cooling_device *cdev);
118
119     This interface function unbind a thermal cooling device from the certain
120     trip point of a thermal zone device. This function is usually called in
121     the thermal zone device .unbind callback.
122     tz: the thermal zone device
123     cdev: thermal cooling device
124     trip: indicates which trip point the cooling devices is associated with
125           in this thermal zone.
126
127 1.4 Thermal Zone Parameters
128 1.4.1 struct thermal_bind_params
129     This structure defines the following parameters that are used to bind
130     a zone with a cooling device for a particular trip point.
131     .cdev: The cooling device pointer
132     .weight: The 'influence' of a particular cooling device on this
133              zone. This is relative to the rest of the cooling
134              devices. For example, if all cooling devices have a
135              weight of 1, then they all contribute the same. You can
136              use percentages if you want, but it's not mandatory. A
137              weight of 0 means that this cooling device doesn't
138              contribute to the cooling of this zone unless all cooling
139              devices have a weight of 0. If all weights are 0, then
140              they all contribute the same.
141     .trip_mask:This is a bit mask that gives the binding relation between
142                this thermal zone and cdev, for a particular trip point.
143                If nth bit is set, then the cdev and thermal zone are bound
144                for trip point n.
145     .limits: This is an array of cooling state limits. Must have exactly
146          2 * thermal_zone.number_of_trip_points. It is an array consisting
147          of tuples <lower-state upper-state> of state limits. Each trip
148          will be associated with one state limit tuple when binding.
149          A NULL pointer means <THERMAL_NO_LIMITS THERMAL_NO_LIMITS>
150          on all trips. These limits are used when binding a cdev to a
151          trip point.
152     .match: This call back returns success(0) if the 'tz and cdev' need to
153             be bound, as per platform data.
154 1.4.2 struct thermal_zone_params
155     This structure defines the platform level parameters for a thermal zone.
156     This data, for each thermal zone should come from the platform layer.
157     This is an optional feature where some platforms can choose not to
158     provide this data.
159     .governor_name: Name of the thermal governor used for this zone
160     .no_hwmon: a boolean to indicate if the thermal to hwmon sysfs interface
161                is required. when no_hwmon == false, a hwmon sysfs interface
162                will be created. when no_hwmon == true, nothing will be done.
163                In case the thermal_zone_params is NULL, the hwmon interface
164                will be created (for backward compatibility).
165     .num_tbps: Number of thermal_bind_params entries for this zone
166     .tbp: thermal_bind_params entries
167
168 2. sysfs attributes structure
169
170 RO      read only value
171 RW      read/write value
172
173 Thermal sysfs attributes will be represented under /sys/class/thermal.
174 Hwmon sysfs I/F extension is also available under /sys/class/hwmon
175 if hwmon is compiled in or built as a module.
176
177 Thermal zone device sys I/F, created once it's registered:
178 /sys/class/thermal/thermal_zone[0-*]:
179     |---type:                   Type of the thermal zone
180     |---temp:                   Current temperature
181     |---mode:                   Working mode of the thermal zone
182     |---policy:                 Thermal governor used for this zone
183     |---trip_point_[0-*]_temp:  Trip point temperature
184     |---trip_point_[0-*]_type:  Trip point type
185     |---trip_point_[0-*]_hyst:  Hysteresis value for this trip point
186     |---emul_temp:              Emulated temperature set node
187     |---sustainable_power:      Sustainable dissipatable power
188     |---k_po:                   Proportional term during temperature overshoot
189     |---k_pu:                   Proportional term during temperature undershoot
190     |---k_i:                    PID's integral term in the power allocator gov
191     |---k_d:                    PID's derivative term in the power allocator
192     |---integral_cutoff:        Offset above which errors are accumulated
193     |---slope:                  Slope constant applied as linear extrapolation
194     |---offset:                 Offset constant applied as linear extrapolation
195
196 Thermal cooling device sys I/F, created once it's registered:
197 /sys/class/thermal/cooling_device[0-*]:
198     |---type:                   Type of the cooling device(processor/fan/...)
199     |---max_state:              Maximum cooling state of the cooling device
200     |---cur_state:              Current cooling state of the cooling device
201
202
203 Then next two dynamic attributes are created/removed in pairs. They represent
204 the relationship between a thermal zone and its associated cooling device.
205 They are created/removed for each successful execution of
206 thermal_zone_bind_cooling_device/thermal_zone_unbind_cooling_device.
207
208 /sys/class/thermal/thermal_zone[0-*]:
209     |---cdev[0-*]:              [0-*]th cooling device in current thermal zone
210     |---cdev[0-*]_trip_point:   Trip point that cdev[0-*] is associated with
211     |---cdev[0-*]_weight:       Influence of the cooling device in
212                                 this thermal zone
213
214 Besides the thermal zone device sysfs I/F and cooling device sysfs I/F,
215 the generic thermal driver also creates a hwmon sysfs I/F for each _type_
216 of thermal zone device. E.g. the generic thermal driver registers one hwmon
217 class device and build the associated hwmon sysfs I/F for all the registered
218 ACPI thermal zones.
219
220 /sys/class/hwmon/hwmon[0-*]:
221     |---name:                   The type of the thermal zone devices
222     |---temp[1-*]_input:        The current temperature of thermal zone [1-*]
223     |---temp[1-*]_critical:     The critical trip point of thermal zone [1-*]
224
225 Please read Documentation/hwmon/sysfs-interface for additional information.
226
227 ***************************
228 * Thermal zone attributes *
229 ***************************
230
231 type
232         Strings which represent the thermal zone type.
233         This is given by thermal zone driver as part of registration.
234         E.g: "acpitz" indicates it's an ACPI thermal device.
235         In order to keep it consistent with hwmon sys attribute; this should
236         be a short, lowercase string, not containing spaces nor dashes.
237         RO, Required
238
239 temp
240         Current temperature as reported by thermal zone (sensor).
241         Unit: millidegree Celsius
242         RO, Required
243
244 mode
245         One of the predefined values in [enabled, disabled].
246         This file gives information about the algorithm that is currently
247         managing the thermal zone. It can be either default kernel based
248         algorithm or user space application.
249         enabled         = enable Kernel Thermal management.
250         disabled        = Preventing kernel thermal zone driver actions upon
251                           trip points so that user application can take full
252                           charge of the thermal management.
253         RW, Optional
254
255 policy
256         One of the various thermal governors used for a particular zone.
257         RW, Required
258
259 trip_point_[0-*]_temp
260         The temperature above which trip point will be fired.
261         Unit: millidegree Celsius
262         RO, Optional
263
264 trip_point_[0-*]_type
265         Strings which indicate the type of the trip point.
266         E.g. it can be one of critical, hot, passive, active[0-*] for ACPI
267         thermal zone.
268         RO, Optional
269
270 trip_point_[0-*]_hyst
271         The hysteresis value for a trip point, represented as an integer
272         Unit: Celsius
273         RW, Optional
274
275 cdev[0-*]
276         Sysfs link to the thermal cooling device node where the sys I/F
277         for cooling device throttling control represents.
278         RO, Optional
279
280 cdev[0-*]_trip_point
281         The trip point with which cdev[0-*] is associated in this thermal
282         zone; -1 means the cooling device is not associated with any trip
283         point.
284         RO, Optional
285
286 cdev[0-*]_weight
287         The influence of cdev[0-*] in this thermal zone. This value
288         is relative to the rest of cooling devices in the thermal
289         zone. For example, if a cooling device has a weight double
290         than that of other, it's twice as effective in cooling the
291         thermal zone.
292         RW, Optional
293
294 passive
295         Attribute is only present for zones in which the passive cooling
296         policy is not supported by native thermal driver. Default is zero
297         and can be set to a temperature (in millidegrees) to enable a
298         passive trip point for the zone. Activation is done by polling with
299         an interval of 1 second.
300         Unit: millidegrees Celsius
301         Valid values: 0 (disabled) or greater than 1000
302         RW, Optional
303
304 emul_temp
305         Interface to set the emulated temperature method in thermal zone
306         (sensor). After setting this temperature, the thermal zone may pass
307         this temperature to platform emulation function if registered or
308         cache it locally. This is useful in debugging different temperature
309         threshold and its associated cooling action. This is write only node
310         and writing 0 on this node should disable emulation.
311         Unit: millidegree Celsius
312         WO, Optional
313
314           WARNING: Be careful while enabling this option on production systems,
315           because userland can easily disable the thermal policy by simply
316           flooding this sysfs node with low temperature values.
317
318 sustainable_power
319         An estimate of the sustained power that can be dissipated by
320         the thermal zone. Used by the power allocator governor. For
321         more information see Documentation/thermal/power_allocator.txt
322         Unit: milliwatts
323         RW, Optional
324
325 k_po
326         The proportional term of the power allocator governor's PID
327         controller during temperature overshoot. Temperature overshoot
328         is when the current temperature is above the "desired
329         temperature" trip point. For more information see
330         Documentation/thermal/power_allocator.txt
331         RW, Optional
332
333 k_pu
334         The proportional term of the power allocator governor's PID
335         controller during temperature undershoot. Temperature undershoot
336         is when the current temperature is below the "desired
337         temperature" trip point. For more information see
338         Documentation/thermal/power_allocator.txt
339         RW, Optional
340
341 k_i
342         The integral term of the power allocator governor's PID
343         controller. This term allows the PID controller to compensate
344         for long term drift. For more information see
345         Documentation/thermal/power_allocator.txt
346         RW, Optional
347
348 k_d
349         The derivative term of the power allocator governor's PID
350         controller. For more information see
351         Documentation/thermal/power_allocator.txt
352         RW, Optional
353
354 integral_cutoff
355         Temperature offset from the desired temperature trip point
356         above which the integral term of the power allocator
357         governor's PID controller starts accumulating errors. For
358         example, if integral_cutoff is 0, then the integral term only
359         accumulates error when temperature is above the desired
360         temperature trip point. For more information see
361         Documentation/thermal/power_allocator.txt
362         RW, Optional
363
364 slope
365         The slope constant used in a linear extrapolation model
366         to determine a hotspot temperature based off the sensor's
367         raw readings. It is up to the device driver to determine
368         the usage of these values.
369         RW, Optional
370
371 offset
372         The offset constant used in a linear extrapolation model
373         to determine a hotspot temperature based off the sensor's
374         raw readings. It is up to the device driver to determine
375         the usage of these values.
376         RW, Optional
377
378 *****************************
379 * Cooling device attributes *
380 *****************************
381
382 type
383         String which represents the type of device, e.g:
384         - for generic ACPI: should be "Fan", "Processor" or "LCD"
385         - for memory controller device on intel_menlow platform:
386           should be "Memory controller".
387         RO, Required
388
389 max_state
390         The maximum permissible cooling state of this cooling device.
391         RO, Required
392
393 cur_state
394         The current cooling state of this cooling device.
395         The value can any integer numbers between 0 and max_state:
396         - cur_state == 0 means no cooling
397         - cur_state == max_state means the maximum cooling.
398         RW, Required
399
400 3. A simple implementation
401
402 ACPI thermal zone may support multiple trip points like critical, hot,
403 passive, active. If an ACPI thermal zone supports critical, passive,
404 active[0] and active[1] at the same time, it may register itself as a
405 thermal_zone_device (thermal_zone1) with 4 trip points in all.
406 It has one processor and one fan, which are both registered as
407 thermal_cooling_device. Both are considered to have the same
408 effectiveness in cooling the thermal zone.
409
410 If the processor is listed in _PSL method, and the fan is listed in _AL0
411 method, the sys I/F structure will be built like this:
412
413 /sys/class/thermal:
414
415 |thermal_zone1:
416     |---type:                   acpitz
417     |---temp:                   37000
418     |---mode:                   enabled
419     |---policy:                 step_wise
420     |---trip_point_0_temp:      100000
421     |---trip_point_0_type:      critical
422     |---trip_point_1_temp:      80000
423     |---trip_point_1_type:      passive
424     |---trip_point_2_temp:      70000
425     |---trip_point_2_type:      active0
426     |---trip_point_3_temp:      60000
427     |---trip_point_3_type:      active1
428     |---cdev0:                  --->/sys/class/thermal/cooling_device0
429     |---cdev0_trip_point:       1       /* cdev0 can be used for passive */
430     |---cdev0_weight:           1024
431     |---cdev1:                  --->/sys/class/thermal/cooling_device3
432     |---cdev1_trip_point:       2       /* cdev1 can be used for active[0]*/
433     |---cdev1_weight:           1024
434
435 |cooling_device0:
436     |---type:                   Processor
437     |---max_state:              8
438     |---cur_state:              0
439
440 |cooling_device3:
441     |---type:                   Fan
442     |---max_state:              2
443     |---cur_state:              0
444
445 /sys/class/hwmon:
446
447 |hwmon0:
448     |---name:                   acpitz
449     |---temp1_input:            37000
450     |---temp1_crit:             100000
451
452 4. Event Notification
453
454 The framework includes a simple notification mechanism, in the form of a
455 netlink event. Netlink socket initialization is done during the _init_
456 of the framework. Drivers which intend to use the notification mechanism
457 just need to call thermal_generate_netlink_event() with two arguments viz
458 (originator, event). The originator is a pointer to struct thermal_zone_device
459 from where the event has been originated. An integer which represents the
460 thermal zone device will be used in the message to identify the zone. The
461 event will be one of:{THERMAL_AUX0, THERMAL_AUX1, THERMAL_CRITICAL,
462 THERMAL_DEV_FAULT}. Notification can be sent when the current temperature
463 crosses any of the configured thresholds.
464
465 5. Export Symbol APIs:
466
467 5.1: get_tz_trend:
468 This function returns the trend of a thermal zone, i.e the rate of change
469 of temperature of the thermal zone. Ideally, the thermal sensor drivers
470 are supposed to implement the callback. If they don't, the thermal
471 framework calculated the trend by comparing the previous and the current
472 temperature values.
473
474 5.2:get_thermal_instance:
475 This function returns the thermal_instance corresponding to a given
476 {thermal_zone, cooling_device, trip_point} combination. Returns NULL
477 if such an instance does not exist.
478
479 5.3:thermal_notify_framework:
480 This function handles the trip events from sensor drivers. It starts
481 throttling the cooling devices according to the policy configured.
482 For CRITICAL and HOT trip points, this notifies the respective drivers,
483 and does actual throttling for other trip points i.e ACTIVE and PASSIVE.
484 The throttling policy is based on the configured platform data; if no
485 platform data is provided, this uses the step_wise throttling policy.
486
487 5.4:thermal_cdev_update:
488 This function serves as an arbitrator to set the state of a cooling